Buried box-type substation
Product Parameters
Performance characteristics
1. Fully considering the particularity of heat dissipation conditions, the transformer adopts low loss and low temperature design, and the top oil temperature is controlled at about 45K, which is far lower than the national standard of 60K;
2. High and low voltage inlet and outlet lines adopt waterproof, fully sealed, fully insulated and fully shielded wiring mode;
3. The box shell is made of anti-corrosion stainless steel, fully sealed, and can be immersed in water for a period of time;
4. The protection system fully considers the convenience of operation and safety;
Suitable for urban environment (installed in the basement or cellar), especially suitable for densely populated central cities.
Technical parameters
|
Serial Number |
Project |
Unit |
Technical parameters |
|
|
1 |
Rated voltage |
High pressure side |
kV |
12 |
|
Low pressure side |
kV |
0.4 |
||
|
2 |
Rated capacity |
kVA |
30~1600 |
|
|
3 |
Wiring mode |
|
D,yn11(Y,yn0) |
|
|
4 |
Rated frequency |
Hz |
50 |
|
|
5 |
Pressure regulating range |
|
±2x2.5%、±5% |
|
|
6 |
Noise level |
dB |
≤ 40 |
|
|
7 |
1min power frequency withstand voltage |
High pressure side |
kV |
35 |
|
Low pressure side |
kV |
5 |
||
|
8 |
Lightning impulse withstand voltage (peak) |
full wave |
kV |
75 |
|
chopping wave |
kV |
85 |
||
|
9 |
Enclosure protection class |
Meet the requirements of national standards |
||