40.5kV ZGS Combined Substation (American)
Product Parameters
Performance characteristics
(1) small size, small footprint, easy to place, easy to camouflage, easy to coordinate with the environment of the community.
(2) Shorten the length of the low-voltage cable, reduce line loss, but also reduce the cost of supporting power supply.
(3) fully sealed, fully insulated structure, no insulation distance, reliable to ensure personal safety.
(4) It can be used for ring network and terminal, and the conversion is flexible and convenient, which improves the reliability of power supply.
(5) The high-voltage incoming line adopts fully insulated, fully sealed, fully shielded and touchable elbow cable connector, which is convenient and flexible to operate, can be plugged and unplugged with load, and has the characteristics of isolating switch.
(6) Using double fuse protection to reduce operating costs.
(7) can be selected according to the need of high ignition point oil can be placed in the building.
(8) The box adopts anti-corrosion design and special painting treatment, which can be operated in various harsh environments for a long time, such as storms and high pollution areas.
Technical parameters
|
Serial Number |
Project |
Unit |
Technical parameters |
||
|
1 |
Transformer main body |
HV side rated voltage |
kV |
40.5 |
|
|
LV side rated voltage |
kV |
0.4/0.69/0.8/1.14 |
|||
|
2 |
Rated capacity |
kVA |
50~1600 |
||
|
3 |
Wiring mode |
|
D,yn11/Y,yn0 |
||
|
4 |
Rated frequency |
Hz |
50 |
||
|
5 |
No-load tap changer |
kV |
±2x2.5% ±5% |
||
|
6 |
Noise level |
dB |
Meet the requirements of national standards |
||
|
7 |
oil surface temperature rise |
K |
≤ 53 |
||
|
8 |
1min power frequency withstand voltage |
High pressure side |
kV |
85 |
|
|
Low pressure side |
kV |
5 |
|||
|
9 |
Lightning impulse withstand voltage (peak) |
full wave |
kV |
200 |
|
|
chopping wave |
kV |
220 |
|||
|
10 |
Cooling mode |
|
oil-immersed self-cooling |
||
|
11 |
HV load switch |
Rated voltage |
kV |
40.5 |
|
|
12 |
Rated current |
A |
630 |
||
|
13 |
Rated short-time withstand current (4S) |
kA |
25/31.5 |
||
|
14 |
Rated short-time closing current |
kA |
63/80 |
||
|
15 |
Breaking times at full load |
Times |
100 |
||
|
16 |
Mechanical life |
Times |
2000 |
||
|
17 |
|
Power frequency withstand voltage (phase to ground) |
|
95 |
|
|
18 |
Enclosure protection class |
Meet the requirements of national standards |
|||