C- GIS SF6 gas insulated metal enclosed high voltage switchgear
Product Parameters
Performance characteristics
1. Strong insulation performance
SF6 gas is used as the insulating medium, which has strong insulation performance and can withstand the impact of high voltage and high current;
2. Strong breaking capacity
The equipment adopts a metal closed structure, and the arc extinguishing chamber of the circuit breaker is placed in a closed metal shell, so that the arc generated when the fault current is broken can be quickly extinguished, and the breaking capacity of the circuit breaker is improved;
3. Long mechanical life
The operating mechanism of the equipment adopts high-quality spring operating mechanism, which has a long mechanical life and can ensure the long-term stable operation of the switchgear;
4, high security
The equipment has perfect safety protection devices, such as over-current protection, over-voltage protection, under-voltage protection, etc., which can detect and deal with abnormal situations in time and improve the safety of the equipment;
5. Easy maintenance
The structure of the equipment is simple, which reduces the maintenance cost of the equipment;
6. Compact design
Small footprint, saving land investment.
Technical parameters
|
Serial Number |
Name |
Parameters |
Parameters |
|
|
1 |
Rated voltage |
12kV |
40.5kV |
|
|
2 |
Rated frequency |
50Hz |
50Hz |
|
|
3 |
Rated current |
630、1250、2500A |
630、1250、2500A |
|
|
5 |
Rated short-circuit breaking current |
25kA;31.5kA; |
25kA;31.5kA; |
|
|
6 |
Rated short-circuit closing current |
63kA;80kA; |
80kA |
|
|
7 |
Rated short-time withstand current/time |
25kA/4S;31.5kA/4S |
31.5kA/4S |
|
|
8 |
Rated peak withstand current peak |
63kA ;80kA ; |
80kA |
|
|
9 |
Rated short-time power frequency withstand voltage |
Interphase and to the ground |
42kV/1min |
95kV/1min |
|
fracture |
48kV/1min |
118kV/1min |
||
|
10 |
Rated lightning impulse withstand voltage peak |
Interphase and to the ground |
75kV |
185kV |
|
fracture |
85kV |
215kV |
||
|
11 |
insulating gas |
SF6 |
SF6 |
|
|
12 |
annual leakage rate |
≤ 0.05% |
≤ 0.05% |
|
|
13 |
Rated operating sequence |
0-0.3s-CO-180s-CO |
0-0.3s-CO-180s-CO |
|
|
14 |
Protection level |
Gas box: IP67; Housing: IP4X |
Gas box: IP67; Housing: IP4X |
|