FZW28 outdoor high voltage vacuum load switch
Product Parameters
Performance characteristics
(1) The outer box body includes the box body, the box cover and the mechanism cover, with good sealing performance, protection level of IP67, moisture-proof, anti-condensation performance, especially suitable for use in high temperature and humid areas.
(2) The connection of the main circuit of the switch adopts a highly reliable cable die-cast tapered inlet and outlet bushing. The length of the inlet and outlet cables is greater than 2 meters, and terminal bushing can also be selected.
(3) The operating mechanism can be operated manually and electrically, making the operation more flexible.
(4) The main circuit of the switch and the operating mechanism are sealed in a box filled with SF6 gas medium, which is not affected by external environmental conditions and can achieve maintenance-free.
(5) The switch is equipped with a three-phase integrated current transformer with zero sequence for protection and measurement to realize line overcurrent protection and line current measurement. The transformation ratio and accuracy of the transformer can be selected according to user requirements.
(6) "Four remote" function: It can be matched with the controller to realize remote control, telemetry, remote signaling and remote adjustment functions.
Technical parameters
|
Serial Number |
Name |
Parameters |
|
|
1 |
Type or model |
Vacuum load switch, FZW □ |
|
|
2 |
Rated voltage (kV) |
12 |
|
|
3 |
Rated current (A) |
630 |
|
|
4 |
Rated frequency (Hz) |
50 |
|
|
5 |
Rated short-time withstand current and duration (kA/s) |
20/4 |
|
|
6 |
Rated peak withstand current (Ka) |
50 |
|
|
7 |
Rated active load breaking current (A) |
630 |
|
|
8 |
Rated short-circuit closing current (kA) |
50 |
|
|
9 |
Rated power frequency 1min withstand voltage (kV) |
Relative ground/interphase |
42 |
|
Interfracture |
48 |
||
|
10 |
Rated lightning impulse withstand voltage Peak (kV) |
Relative ground/interphase |
75 |
|
Interfracture |
85 |
||
|
11 |
1min power frequency withstand voltage of secondary circuit (KV) |
2 |
|
|
12 |
Mechanical life (times) |
5000 |
|
|
13 |
Rated active load breaking times |
≥ 100 |
|
|
14 |
Temperature rise test current |
1.1x630 |
|
|
15 |
Enclosure protection class |
IP67 |
|
|
16 |
Operating mechanism |
Spring/Electromagnetic |
|
|
17 |
Operation mode |
Manual/electric |
|
|
18 |
Operating voltage |
AC/DC 220V、110V、48V、24V |
|
|
19 |
Transport weight (kg) |
125 |
|