A secondary fusion set of on-column circuit breakers
Product Parameters
Product overview
There are mainly the following types
ZW32-12/T630-20 secondary fusion column vacuum circuit breaker common electromagnetic type;
ZW32-12/T630-20S secondary fusion column vacuum circuit breaker digital type;
ZW32-12/T630-20R secondary fusion column vacuum circuit breaker deep fusion type;
|
Silicone insulated pole |
The vacuum interrupter, the main electric circuit, the insulation support, etc. are organically combined with a silicone insulation pole.
|
Transformer |
Divided into three types: magnetic, digital and built-in deep fusion
Electromagnetic:
The common electromagnetic type of vacuum circuit breaker on the first and second fusion column integrates and packages high-precision current transformer and voltage sensor into one, and is fixed on the outside of the pole column. The transformer has wide combined measurement range, high measurement accuracy, high reliability and complete analog quantity. It cooperates with feeder terminal (FTU) and line loss module to realize line loss measurement and accurate determination of various line faults to meet the supporting requirements of power distribution automation;
Digital:
The digital type of vacuum circuit breaker on the first and second fusion column integrates and packages high-precision electronic current and voltage sensors into one, and is fixed on the outside of the pole. The ADMU digital-to-analog conversion module is installed outside the mechanism box body to directly convert the current and voltage signals of the line into digital signals and transmit them to the digital intelligent controller. The structure is cylindrical, reducing the power consumption of the whole machine and increasing the reliability of the complete set of the equipment.
Deep Fusion:
The vacuum circuit breaker on the primary and secondary fusion column is a deep fusion type, which casts and seals the high-precision current transformer and voltage sensor, the vacuum interrupter and the insulating support pole into a whole. The sealing body can provide a stable and anti-interference working environment for the transformer, ensure more accurate output signal, and have the advantages of high protection level, simple installation and small volume.
|
Operating mechanism |
Spring operating mechanism: the circuit breaker adopts a miniaturized spring operating mechanism, which has low energy consumption for opening and closing; the mechanism transmission adopts a direct drive mode, with small opening and closing components and high reliability.
Permanent magnet operating mechanism, this mechanism greatly reduces the dispersion and uncontrollability of the action time, has high reliability, can be operated frequently for a long time, and truly achieves permanent maintenance-free.
|
Box |
The circuit breaker box is made of high-quality stainless steel plate, and the surface can be sprayed with plastic protection according to user requirements. It adopts a fully enclosed structure with good sealing performance, which helps to improve moisture-proof, rust-proof, and condensation-proof performance, and improves the reliability of the mechanism. All structures meet the requirements of the State Grid's first and second convergence standardization program.
Secondary Interface
The secondary interface designed according to the national network standardization scheme adopts military grade aviation sockets, aviation plugs and cables adopt fully sealed waterproof structure, and the welding wire side is sealed with insulating materials, with strong condensation resistance. The cable break at the connection is specially treated and fixed to effectively prevent rainwater from intruding and has a very high protection level.
Power supply
The vacuum circuit breaker on the first and second fusion column can not only use electromagnetic voltage transformer as the working power supply of the complete set of equipment, but also provide the working power supply for the complete set of equipment by means of capacitor power extraction. The power extraction device can be built in the solid sealing pole column (deep fusion type) or externally placed on the mechanism box body. After using the power extraction device, independent electromagnetic voltage transformer prone to failure can be omitted, simplifying the equipment structure, high reliability and easy installation.
Multiple protection monitoring functions
It has the function of calculating active power, reactive power, power factor, frequency and electric energy; it has the function of self-adaptive integrated local feeder automation to realize local line selection, area positioning and isolation of single-phase ground fault, and to realize the isolation of fault area and the restoration of power supply in non-fault area through reclosing;
Performance characteristics
(1) The circuit breaker on the secondary fusion pole is composed of the outdoor circuit breaker switch body on the pole, the HZD300F feeder terminal (FTU), the power voltage transformer and the connecting cable. The switch body, the feeder terminal and the power voltage transformer are connected by the aviation connector through the outdoor fully insulated cable;
(2) High-precision protection CT, zero-sequence CT and zero-sequence voltage sensors, with wide measurement range, high measurement accuracy, high reliability and complete analog quantity, cooperate with HZD300F feeder terminal (FTU) and line loss module to realize line loss measurement and accurate determination of various faults of the line to meet supporting requirements;
(3) Military-grade aviation socket, aviation plug and cable adopt fully sealed waterproof structure, and the welding wire side adopts insulating material sealing treatment, with strong condensation resistance; The cable break at the connection is specially treated and fixed to effectively prevent rainwater from immersing and has a very high protection level;
(4) It has the function of calculating active power, reactive power, power factor, frequency and electrical energy; it has the function of adaptive integrated local feeder automation to realize local line selection, regional positioning and isolation of single-phase ground fault, and to realize fault area isolation and non-fault area restoration of power supply through reclosing;
(5) The structure is compact, the layout is reasonable, and the functions are complete. The configuration indicators fully meet the requirements of the State Grid's first and second integration sets, which is convenient for unified procurement and management.
Technical parameters
Technical parameters of post circuit breaker body
|
Serial Number |
Name |
Parameters |
|
|
1 |
Type or model |
Vacuum circuit breaker |
|
|
2 |
Rated voltage (kV) |
12 |
|
|
3 |
Rated current (A) |
630 |
|
|
4 |
Rated frequency (Hz) |
50 |
|
|
5 |
Rated short-circuit breaking current (kA) |
20、25 |
|
|
6 |
Rated short-time withstand current and duration (kA/s) |
20/4 、25/4 |
|
|
7 |
Rated peak withstand current (kA) |
50、63 |
|
|
8 |
Rated short-circuit breaking current (kA) |
20、25 |
|
|
9 |
Rated short-circuit closing current (kA) |
50、63 |
|
|
10 |
Rated power frequency 1min withstand voltage (kV) |
Relative ground/interphase |
42 |
|
Interfracture |
48 |
||
|
11 |
Rated lightning impulse withstand voltage Peak (kV) |
Relative ground/interphase |
75 |
|
Interfracture |
85 |
||
|
12 |
1min power frequency withstand voltage of secondary circuit (KV) |
2 |
|
|
13 |
Mechanical life (times) |
10000 |
|
|
14 |
Rated short-circuit breaking current breaking times (times) |
≥ 30 times |
|
|
15 |
Temperature rise test current |
1.2x630 |
|
|
16 |
Operating mechanism |
spring/permanent magnet/magnetic control |
|
|
17 |
Operation mode |
Manual/electric |
|
|
18 |
Operating voltage |
DC24\110\220,AC220 |
|
|
19 |
Transport weight (kg) |
120 |
|
HZD300F30 intelligenceFeeder Terminal (FTU)Technical parameters
|
Serial Number |
Name |
Parameters |
|
|
1 |
Nominal value of voltage input |
AC100V or AC 220V optional |
|
|
2 |
Nominal value of current input |
AC 1A or AC 5A optional |
|
|
3 |
Working power supply |
AC220V, 2-way |
|
|
4 |
Measurement and control capacity |
|
|
|
5 |
Voltage measurement accuracy |
0.5 level |
|
|
6 |
Current measurement accuracy |
0.5 grade (≤ 1.2In),5P10(≤ 10In). |
|
|
7 |
Accuracy of active power and reactive power |
Level 1 |
|
|
8 |
Remote communication power supply |
DC 24V self-provided remote communication power supply, no external matching |
|
|
9 |
Remote communication resolution |
≤ 2ms |
|
|
10 |
Software anti-jitter time |
10~1000ms can be set |
|
|
11 |
Overload capacity of AC current circuit |
1.2In continuous operation, 20In,1s |
|
|
12 |
Overload capacity of AC voltage circuit |
1.2Un continuous work |
|
|
13 |
punctuality accuracy |
Every 24 hours error 2s |
|
|
14
|
Control output |
Rated power of contact |
AC 250V/5A, DC 80V/2A, or DC 110V/0.5A pure resistance load |
|
Contact life |
Not less than 10.5Times |
||
|
15
|
Communication Interface |
serial port |
Two |
|
RJ45 Ethernet port |
Two |
||
|
16 |
communication protocol |
101 and 104 Communication Protocol of DL/T 634 Standard and Regional Standard of South Network |
|
|
17 |
Terminal power consumption |
|
|
|
18 |
Supporting power supply |
Power Management Module |
Long-term stable output ≥ 50W, short-term output ≥ 300W/15s |
|
Communication power supply |
Rated DC24V, long-term stable output ≥ 15W, instantaneous output ≥ 20W/50ms |
||
|
Operating power |
According to the different operating mechanism supporting the appropriate operating power DC24V, AC220V |
||
|
19 |
Backup power mode |
Maintenance-free valve-regulated lead-acid battery/super capacitor DC24V |
|
|
20 |
Terminal shell |
Box structure or cover structure optional (cover structure includes backup power supply enclosure) |
|
|
21 |
Installation method |
Pole/Tower Hanging Installation |
|
|
22 |
Interface mode |
aviation connector |
|
|
23 |
Average trouble-free working time |
≥ 50000h |
|