ZW32 outdoor high voltage vacuum circuit breaker
Product Parameters
Performance characteristics
(1) The three-phase pillar structure is adopted, which has the characteristics of stable and reliable breaking performance, no combustion and explosion hazard, maintenance-free, small size, light weight and long life.
(2) The three-phase pillar adopts silicone rubber solid insulation; it improves the insulation performance and anti-pollution, anti-condensation ability, and improves the ozone resistance, anti-ultraviolet, anti-aging ability, and also greatly improves the mechanical strength.
(3) The circuit breaker can adopt a spring operating mechanism, and the opening and closing energy consumption is low; the mechanism transmission adopts a direct drive mode, the opening and closing parts are small, and the reliability is high. The permanent magnet operating mechanism can also be used, which greatly reduces the dispersion and uncontrollability of the action time, has high reliability, can be operated frequently for a long time, and truly achieves permanent maintenance-free.
(4) The circuit breaker box is made of high-quality stainless steel plate, and the surface can be sprayed with plastic protection according to user requirements. It adopts a fully enclosed structure with good sealing performance, which helps to improve moisture resistance, rust resistance, and condensation prevention performance, and improves the performance of the organization. reliability.
(5) "Four remote" function: It can be matched with the controller to realize remote control, telemetry, remote signaling and remote adjustment functions.
Technical parameters
|
Serial Number |
Name |
Parameters |
|
|
1 |
Type or model |
Vacuum circuit breaker |
|
|
2 |
Rated voltage (kV) |
12 |
|
|
3 |
Rated current (A) |
630 |
|
|
4 |
Rated frequency (Hz) |
50 |
|
|
5 |
Rated short-circuit breaking current (kA) |
20、25 |
|
|
6 |
Rated short-time withstand current and duration (kA/s) |
20/4 、25/4 |
|
|
7 |
Rated peak withstand current (Ka) |
50、63 |
|
|
8 |
Rated short-circuit breaking current (kA) |
20、25 |
|
|
9 |
Rated short-circuit closing current (kA) |
50、63 |
|
|
10 |
Rated power frequency 1min withstand voltage (kV) |
Relative ground/interphase |
42 |
|
Interfracture |
48 |
||
|
11 |
Rated lightning impulse withstand voltage Peak (kV) |
Relative ground/interphase |
75 |
|
Interfracture |
85 |
||
|
12 |
1min power frequency withstand voltage of secondary circuit (KV) |
2 |
|
|
13 |
Mechanical life (times) |
10000 |
|
|
14 |
Rated short-circuit breaking current breaking times (times) |
≥ 30 times |
|
|
15 |
Temperature rise test current |
1.2x630 |
|
|
16 |
Operating mechanism |
Spring/Permanent Magnet |
|
|
17 |
Operation mode |
Manual/electric |
|
|
18 |
Operating voltage |
DC24\110\220,AC220 |
|
|
19 |
Transport weight (kg) |
120 |
|